Viessmann · Mini-split

PH90 Evaporator coil too hot

Medium severity Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoorViessmann DLFSHB high wall indoor

What the control is telling you

Indoor coil temperature too high (heating). The manuals give no flow chart; it is a protection stop.

Applies to: DLCM(R/H)B multi-zone outdoor units with DLFSHBH high wall indoor units (Midea, Carrier, Viessmann)

Models that show this code

12 models in Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoor, Viessmann DLFSHB high wall indoor

DLCMHBH24CAKDLCMHBH30DAKDLCMHBH36DAKDLCMHBH48EAKDLCMRBH18BAKDLCMRBH36DAKDLCMRBH48EAKDLFSHBH09XAKDLFSHBH12XAJDLFSHBH12XAKDLFSHBH18XAKDLFSHBH24XAK

Other codes on the same units

  • PC46 Compressor speed out of control
  • PC49 Compressor over-current
  • PCA1 Refrigerant pipe condensation protection
  • PH09 Anti-cold-air in heating
  • PH91 Evaporator coil too cold
  • -- Indoor units mode conflict
  • AP Wi-Fi pairing (AP mode)
  • CL Filter cleaning reminder / Active Clean

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 23 Outdoor Unit Error Display p.26; Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 p.17. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.