PC03 Pressure protection

High severity Viessmann DLFSHB high wall indoor

What the control is telling you

High or low pressure switch tripped (see PC30 / PC31 on the outdoor unit).

Applies to: DLFSHBH high wall indoor units 09-24K (Midea / Carrier / Viessmann) on DLC multi-zone or single-zone outdoor units

Likely causes

  • See PC30 / PC31

Test and repair steps

  1. Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
  2. Check the high-pressure switch wiring to the main board.
  3. Unplug the switch and measure it. A good switch reads 0 ohms at rest; open = replace it.
  4. If outdoor air is above 122 F (50 C), the unit is outside its range: shut it down.
  5. Check outdoor airflow nothing blocking the coil, coil clean, outdoor fan running (see EC07 if not).
  6. Check the refrigerant side (overcharge, restriction). If everything checks out, replace the outdoor main board.

Models that show this code

5 models in Viessmann DLFSHB high wall indoor

DLFSHBH09XAKDLFSHBH12XAJDLFSHBH12XAKDLFSHBH18XAKDLFSHBH24XAK

Other codes on the same units

  • PC00 Inverter module (IPM) protection
  • PC0A Condenser high temperature protection
  • PC0F PFC module protection
  • PC0L Outdoor temperature too low
  • PC04 Inverter compressor drive error
  • PC06 Discharge temperature protection
  • PC08 Outdoor over-current protection
  • PC10 Low AC supply voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 p.17. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.