Viessmann · Mini-split
PC03 Pressure protection
What the control is telling you
High or low pressure switch tripped (see PC30 / PC31 on the outdoor unit).
Applies to: DLFSHBH high wall indoor units 09-24K (Midea / Carrier / Viessmann) on DLC multi-zone or single-zone outdoor units
Likely causes
- See PC30 / PC31
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Check the high-pressure switch wiring to the main board.
- Unplug the switch and measure it. A good switch reads 0 ohms at rest; open = replace it.
- If outdoor air is above 122 F (50 C), the unit is outside its range: shut it down.
- Check outdoor airflow nothing blocking the coil, coil clean, outdoor fan running (see EC07 if not).
- Check the refrigerant side (overcharge, restriction). If everything checks out, replace the outdoor main board.
Models that show this code
5 models in Viessmann DLFSHB high wall indoor
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 p.17. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.