Viessmann · Mini-split
EH 00 EEPROM parameter error (indoor or outdoor)
What the control is telling you
The main chip on the indoor or outdoor PCB is not getting feedback from the EEPROM chip.
Applies to: Indoor and outdoor PCB EEPROM
Likely causes
- EEPROM chip or its connection on the indoor or outdoor PCB has failed
Test and repair steps
- Shut off the power supply and turn it back on 2 minutes later.
- If the code is still displayed, replace the indoor main PCB (E0/EA) or the outdoor main PCB (F4).
- If the code clears, the unit is operating as designed.
- On some models the outdoor PCB cannot be removed alone. Replace the whole outdoor electric control box.
Other codes on the same units
- EC 55 IGBT temperature sensor TH fault
- EC 56 Evaporator coil outlet temperature sensor T2B fault
- EE Water-level alarm malfunction
- EH 03 Indoor fan speed out of normal range
- EH 0A EEPROM parameter error (indoor or outdoor)
- EH 0E Water-level alarm malfunction
- EH 0b Display board to main board communication error
- EH 31 Upper indoor fan speed out of normal range
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLFSFBH Service Manual, p. 16. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.