Trane · Heat pump

Flashing flame icon Second-stage heat energized

Normal status XR103

What the display is showing

Flame icon flashes when 2nd-stage heat (auxiliary or emergency) is on.

Applies to: XR103 thermostat

Settings for these units

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane XR103 installation and user guide 18-HD55D1-1C-EN, p. 8. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.