LC Scale build-up in heat exchanger (LC, LC0–LC9, 00)
What the control is telling you
LC or LC0–LC9 means scale has built up in the heat exchanger and it must be flushed; in the maintenance code history it appears as 00. Newer units lock out until reset.
Applies to: SENSEI RX/CX Series, Non-SENSEI Series
Likely causes
- Scale build-up in the heat exchanger
- Untreated hard water
- Heat exchanger not flushed at the recommended interval
- Repeated temporary resets without flushing (LC# count rising)
Test and repair steps
- Flush the heat exchanger following the owner's manual procedure (section 6.3 on SENSEI RX/CX).
- Treat hard water to prevent further scale and heat exchanger damage.
- Non-SENSEI LC codes are the only codes that let the heater keep running; the display alternates LC and set temperature and the controller keeps beeping.
- Non-SENSEI older products reset LC by switching power off and back on.
- Newer Non-SENSEI and SENSEI RX/CX a built-in shutdown locks the heater out to prevent scale damage, so a reset is required.
- Temporary run until flushing press On/Off on the controller five times (within 5 s on RX/CX). The unit runs ~70 hrs then locks out again; display cycles set temp and LC#. E.g., LC2 = three 70-hr resets without flush.
- After flushing, SENSEI RX/CX LC clears automatically if the flush completes properly; if not, press PC board buttons A and B together for five seconds.
- After flushing, newer Non-SENSEI press PC board buttons A and B together for five seconds.
- The heater returns to normal and the LC# count resets to 0. This hard reset is not listed in the owner's/installation manual or tech sheet.
- SENSEI RX/CX Flushing history can be viewed in the Rinnai Central app.
Settings for these units
RX supply connection sizes · SENSEI RX/CX
| Connection | Size |
|---|---|
| Gas | 3/4 in. MNPT |
| Cold inlet | 3/4 in. MNPT |
| Hot outlet | 3/4 in. MNPT |
| Condensate drain | 1/2 in. MNPT |
Vent connection: 2 in. nominal PVC/CPVC/PP or 3 in./5 in. concentric.
Full specs (input, flow, weight) are only on each model's spec sheet, not in this manual.
RX water quality limits · SENSEI RX/CX
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Water damage beyond these limits is not covered by warranty.
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
- RX temperature settings available · SENSEI RX/CX
- RUCS/RUS unit clearances · Non-SENSEI
- RUCS/RUS water quality limits · Non-SENSEI
Models that show this code
77 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX
Other codes on the same units
- In Initial setting: indoor installation
- In Use fast flash In Use light rapid flash
- In Use slow flash In Use light slow flash
- In Use solid In Use light steady
- LC, LC0-LC9 Code LC, LC0-LC9
- LPG Initial setting: propane (LPG)
- Lock key Controller locked (key symbol)
- Mute Controller key beeps on/off
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.67–68. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.