Rinnai · Combi boiler

Parameter mode Parameter settings menu

Menu / mode display I-Series Plus 150K and smallerI-Series Plus 175K and higher

What the display is showing

Installer menu for changing the boiler's parameters from the PC board. Example in the guide: parameter A2 sets the vent material (A = PVC, B = CPVC, polypropylene or other) for the exhaust temperature limit. Only change what an instruction tells you to change.

Applies to: Rinnai I-Series Plus boilers and combis (150K and smaller, 175K and higher)

What to do

  1. Remove the front panel; the PC board is at the lower left.
  2. Press and hold the left SW1 button for 5 seconds.
  3. Use the up and down arrows to scroll to the parameter, then press Select.
  4. Change the value and press Select to store it.
  5. Press the left SW1 button to leave the menu.

Models that show this code

8 models in I-Series Plus 150K and smaller, I-Series Plus 175K and higher

IP060160CIP090099CIP090160CIP090199CIP120199CIP150199CIP175199CIP199199C

Other codes on the same units

  • ECL Reset complete (gas solenoid circuit)
  • FFF Maintenance performed marker
  • LC Lime condition – flush plate heat exchanger
  • LOC Child lock is on
  • P Venturi reset: first screen
  • PCL Venturi reset accepted
  • Perf data Performance data menu
  • SS Service Soon reminder

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting I-Series Plus Diagnostic Codes (800000375), Code 540 steps 2-5 p.31. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.