Rinnai · Combi boiler

631 DHW recirculation pump – insufficient flow

Medium severity I-Series Plus 150K and smallerI-Series Plus 175K and higher

What the control is telling you

With dedicated recirculation mode selected, the recirculation pump is running but the boiler does not see at least 1.3 GPM of flow.

Applies to: I-Series Plus Combi boilers — 150K BTU and smaller and 175K BTU and higher

Likely causes

  • Recirculation parameters (9, 12, 13) set incorrectly
  • Pump not wired to Pump 4 terminal
  • Blown Pump 4 fuse
  • Hot/cold lines reversed or cross-connected
  • Dirty inlet filter, faulty check valve or air in the recirculation loop
  • Flow turbine/sensor or water flow control problem
  • Undersized or failed recirculation pump

Test and repair steps

  1. Check parameters P9 = b (DHW recirculation on via Pump 4); P12 = A for crossover valve only, b for dedicated recirculation (needs over 1.3 GPM); P13 = A (default; enables external timer control).
  2. If the pump does not run, confirm it is wired to the Pump 4 terminal on the PC Board (external pumps: 120 VAC, max 2 A).
  3. With power off, check the Pump 4 fuse for continuity and replace it if open.
  4. With all fixtures closed, run the recirculation pump and read flow in performance data #7.
  5. If flow reads 0 isolate DHW and open the PRV or service port. If still no flow, check that hot/cold lines are not reversed or cross-connected.
  6. If water flows at the port but data #7 reads 0: confirm the flow turbine spins freely and flow sensor wiring is sound and dry.
  7. Check performance data #13 reads 0 (mid) or 1 (open) while the pump runs; see code 651 for testing the water flow control.
  8. If flow is below 13 (1.3 GPM): clean the inlet water filter, confirm the dedicated return line and its check valve are installed and working, and confirm the flow turbine spins freely.
  9. Bleed all air from the recirculation loop and confirm the pump is sized for the system and the boiler's piping (over 1.3 GPM needed).
  10. Replace the recirculation pump if it is not working.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.34–35. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.