Rinnai · Air handler

Installer menu Installer menu (password protected)

Menu / mode display Canadian Air Handler

What the display is showing

Password-protected menu where a qualified installer changes the operating parameters. It holds the sub-menus for system, cooling/heat pump, fan, pump and delay settings (parameter tables are in the manual's settings section). The Furnace Model entry must be set to CAH050E when a control board is replaced, and Reset System restores factory defaults.

Applies to: Rinnai Canadian hydronic air handler (CAH)

What to do

  1. Enter the password with the buttons in this order: down, center, up, center.
  2. Up/down change menu, line or value; center selects or validates.

Settings for these units

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Canadian Air Handler Installation and Operation Manual (600000023), Software Settings p.41-42. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.