NTI · Boiler
Lockout 82 Stack limit
What the control is telling you
Flue gas temperature at the stack sensor exceeded the stack limit.
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
Likely causes
- Dirty heat exchanger or combustion chamber
- Stack limit setpoint wrong
- Faulty stack sensor
Test and repair steps
- Inspect and clean the combustion chamber and heat exchanger
- Set the stack limit setpoint to the maximum of 220 F (104 C); for PVC exhaust venting in Canada the limit is 149 F (65 C)
- Measure the sensor resistance and compare to the thermistor chart
Models that show this code
13 models in Trinity Tft
Other codes on the same units
- Lockout 60 Internal fault: HFS shorted to LFS
- Lockout 60 Internal fault: HFS shorted to LFS
- Lockout 71 Input power frequency mismatch
- Lockout 82 Stack limit
- Lockout 97 Internal fault: A2D mismatch
- Lockout 97 Internal fault: A2D mismatch
- Lockout 98 Internal fault: Exceeded VSNSR voltage tolerance
- Lockout 98 Internal fault: Exceeded VSNSR voltage tolerance
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.