NTI · Boiler
Hold 62 Fan speed not proved
What the control is telling you
Control does not see the expected blower speed signal. It flashes up briefly before every ignition as the blower drives to light-off speed; only a problem if it stays.
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
Likely causes
- Normal during drive to light-off (momentary)
- Blown fuse A (blower has no power)
- Loose blower wiring or connectors
- Failed blower or control board
Test and repair steps
- Check fuse A
- Check the blower connectors at both the control and the blower
- If the code stays 15 seconds or longer with the blower running, read the fan speed on the display; if it shows LOW RPM, HIGH RPM, 0 or a jumping value, try another control and replace the blower if the code stays
Models that show this code
13 models in Trinity Tft
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.