NTI · Boiler

03 09 Gas relay check failed

High severity TRX

What the control is telling you

The gas relay check on the PCB failed.

Applies to: TRX150

Likely causes

  • Internal PCB fault
  • Gas valve or relay fault

Test and repair steps

  1. Switch the boiler off and back on at the main electrical supply.
  2. If the problem returns, replace the main PCB.

Models that show this code

5 models in TRX

TRX085TRX110CTRX150TRX199TRX199C

Other codes on the same units

  • 03 04 Too many resets in 15 minutes (more than 5)
  • 03 05 PCB internal error
  • 03 06 PCB internal error
  • 03 07 PCB internal error
  • 3 P9 Scheduled maintenance: call for service
  • 4 11 Room sensor open or short circuit, Zone 1
  • 4 12 Room sensor open or short circuit, Zone 2
  • 4 13 Room sensor open or short circuit, Zone 3

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: NTI TRX150 manual, p. 91. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.