03 02 Communication error GP-GIU
What the control is telling you
Communication fault between the main PCB and the HMI.
Applies to: TRX150
Likely causes
- Loose or faulty connection between main PCB and HMI
- Internal PCB fault
Test and repair steps
- Switch the boiler off and back on at the main electrical supply.
- If the problem returns, check the connection between the main PCB and the HMI.
- If the problem still returns, replace the main PCB.
Models that show this code
5 models in TRX
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 91. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.