Midea · Furnace

LED2 green 4 flashes Refrigerant sensor expired or faulty

High severity Midea 96% AFUE A2L Gas Furnace (BGH96M)

What the control is telling you

The refrigerant sensor has reached end of life or is faulty. The Y signal is turned off and cooling stops.

Applies to: Midea BGH96M 96% AFUE two-stage gas furnaces (060B3A, 080B3A, 080C4A, 100C5A, 100D5A, 120D5A) with A2L refrigerant leak sensor on CN30 (fan drive board LED2)

Likely causes

  • Sensor end of service life
  • Sensor failure

Test and repair steps

  1. Confirm the sensor cable and CN30 connection are good.
  2. Order and install a new refrigerant detection sensor from the distributor.
  3. Confirm SW1-2 is ON and cooling resumes.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Midea 96% AFUE Gas Furnace (A2L) Troubleshooting Guide, Appendix A3 Requirements for refrigerant leakage sensors, LED2 table, p.27. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.