Green SLOW flash / Red ON Discharge line temperature fault
What the control is telling you
Should not occur on these units: no discharge sensor is used, a 10K resistor sits on the discharge sensor terminals (COIL-BROWN). A shorted resistor makes the control see high discharge temperature. (The table text says ML14KP1 even in the EL16KP1 manual.)
Applies to: Lennox EL16KP1 (Elite) and ML14KP1 (Merit) R-454B heat pumps, sizes -018 to -060, demand defrost control A108 (CMC1)
Likely causes
- Shorted 10K resistor on the discharge sensor connection
- Wiring short at the discharge sensor terminals
Test and repair steps
- Turn off power and locate the 10K resistor on the discharge sensor connection of the defrost control.
- Measure it with an ohmmeter; it should read about 10K ohms. Replace it if shorted.
- Check that the resistor leads are not touching each other or the board.
- Cycle 24 VAC power and confirm the code clears.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL16KP1 Unit Information 100195 / ML14KP1 Unit Information 100108, Table 4 Demand Defrost Control (A108) Diagnostic LEDs, p.32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.