Lennox · Heat pump
E437 Inverter heat-sink temperature sensor fault (inverter code 65)
What the control is telling you
Heat sink sensor reads below 4 F or above 264 F after 10 minutes of operation; unit stops. Five times in an hour = lockout. Inverter LED flash code 65 (red 6 flashes, green 5 flashes). S30/S40 thermostat alert code 437 (shown as E437 on the unit control display).
Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Failed heat sink sensor / inverter
Test and repair steps
- Refer to the unit service manual.
- Service urgent disconnect and reconnect power to the outdoor unit to clear.
- Check inverter LEDs flash code 65 = red 6 flashes, green 5 flashes. Normal inverter LEDs with no fault: red ON, green OFF.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.41. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.