Lennox · Heat pump
E432 Inverter DC link high voltage (inverter code 28)
What the control is telling you
DC link capacitor voltage above 480 VDC; unit stops. 10 times in 60 minutes = lockout. Inverter LED flash code 28 (red 2 flashes, green 8 flashes). S30/S40 thermostat alert code 432 (shown as E432 on the unit control display).
Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- High input voltage
- Inverter fault
- Compressor wiring or winding fault
Test and repair steps
- Check U, V, W connections at the inverter and compressor.
- Check compressor winding resistance and ground.
- Check input power single phase 208/230 VAC +10%.
- Check DC link and MICOM sensing voltage; replace inverter if out of range.
- Clear by disconnecting power to the outdoor unit and restarting.
- Check inverter LEDs flash code 28 = red 2 flashes, green 8 flashes. Normal inverter LEDs with no fault: red ON, green OFF.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.37. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.