Lennox · Heat pump
E427 Inverter DC peak fault (inverter code 21)
What the control is telling you
DC peak current of 55 A or higher detected; compressor and fan stop. 10 times in an hour = lockout. Inverter LED flash code 21 (red 2 flashes, green 1 flash). S30/S40 thermostat alert code 427 (shown as E427 on the unit control display).
Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Compressor current spike at restart
- Older inverter software (XP20/XP25 at defrost entry/exit)
Test and repair steps
- XP20/XP25 built before serial number 5817F with frequent 427: compare the inverter part number with the latest in repair parts and replace if needed (newer software has current slope logic).
- Serial format PPYYMNNNNN YY and M are year and month built.
- Refer to the unit service manual.
- Clear by disconnecting and reconnecting power to the outdoor control.
- Check inverter LEDs flash code 21 = red 2 flashes, green 1 flash. Normal inverter LEDs with no fault: red ON, green OFF.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.