Lennox · Heat pump

E115 Low secondary (24 VAC) voltage

High severity

What the control is telling you

24 VAC to a component control is below the required 18 to 30 VAC range. S30/S40 thermostat alert code 115 (shown as E115 on the unit control display).

Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • Overloaded transformer (power-robbing accessories)
  • Low line voltage
  • Loose wiring

Test and repair steps

  1. Measure 24 VAC at the control and correct it.
  2. Look for extra accessories loading the transformer.
  3. A larger or additional VA transformer may be needed.
  4. Damper module runs non-zone mode until voltage is restored.
  5. Clears automatically once fixed.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.16. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.