Lennox · Heat pump
32 Device resetting
What the control is telling you
A component is resetting itself, often during a power outage or fluctuation (information for dealer only). S30/S40 thermostat alert code 32.
Applies to: Lennox communicating heat pumps incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Power fluctuation
- Overloaded transformer
- Low 24 VAC at device
- Failing control
Test and repair steps
- Check the power connections.
- Check amp draw at the transformer for overload.
- Check 24 VAC at the device.
- If it continues after checking connections, replace that control.
- To clear by hand on an S30 go to Menu > Settings > Advanced Settings, open View Dealer Control Center, tap Notifications, pick the code and tap Clear.
Settings for these units
- Outdoor unit clearances · Lennox EL16KP1
- Outdoor unit clearances · Lennox ML14KP1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.