Lennox · Furnace
35 Incorrect operation of device
What the control is telling you
The unit did not respond within 15 minutes to a thermostat request to start or stop heating/cooling; a device was disabled by a fault/lockout, or electrical noise from the contactor coil disrupted communication. S30/S40 thermostat alert code 35.
Applies to: Lennox communicating gas furnaces (e.g. SL280UHV/SL280UHNV, EL296UHV) in S30/S40 smart thermostat systems
Likely causes
- Device in fault/lockout
- Electrical noise when the compressor contactor coil energizes
Test and repair steps
- Check the device's own fault/lockout code and fix that first.
- On a communicating system, add a transient voltage suppressor across (parallel to) the coil terminals of the outdoor unit's compressor contactor.
- Non-communicating outdoor unit wire suppressor 89W72 across the contactor coil or across Y1 and C at the indoor control.
- Suppressor part Littelfuse 5KP43CA bidirectional TVS diode; see Lennox note IAQ-10-01.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox ML180UHE
- Filter sizes (filter rack kits) · Lennox EL195UHNE
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.11. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.