Lennox · Air conditioner
E125 Control hardware problem
What the control is telling you
A hardware problem on a component control. S30/S40 thermostat alert code 125 (shown as E125 on the unit control display).
Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Failed control board
- EIM: jumper left between R and W2 on indoor unit
- PureAir S: jumper selector missing
Test and repair steps
- Zoning system stays in non-zone mode (dampers open) for five minutes after the condition ends.
- With an Equipment Interface Module, remove any jumper between R and W2 on the indoor unit.
- With PureAir S, install the missing control board jumper selector.
- Otherwise replace the control if the problem is persistent and stops operation.
- Clears five minutes after the issue ends.
Settings for these units
- Outdoor unit clearances · Lennox EL16KC1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.17. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.