Lennox · Air conditioner
E114 AC line frequency / distortion problem
What the control is telling you
Power to a component has a frequency or distortion problem; often transformer phasing, input power or overloading. Air handler control flags it when frequency is below 57 Hz or above 63 Hz for 10 seconds. S30/S40 thermostat alert code 114 (shown as E114 on the unit control display).
Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Generator with bad frequency
- Transformer overload or phasing
- Severe line distortion
Test and repair steps
- Check line voltage and frequency; if running on a generator, check its frequency.
- Correct voltage and frequency problems.
- Outputs are disabled (service soon); after 10 minutes it escalates. Damper module runs central mode only until fixed.
- With Lennox Smart Zoning set the damper module transformer jumper to system transformer, check wiring, replace the 40 VA furnace transformer with a 70 VA one, recommission.
- Note outdoor unitary controls do not display 114.
- Normal operation resumes five seconds after recovery.
Settings for these units
- Outdoor unit clearances · Lennox EL16KC1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.16. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.