Lennox · Air conditioner

700 Thermostat temperature sensor problem

High severity

What the control is telling you

Built-in temp sensor in the HD display is faulty. S30/S40 alert code 700.

Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • Display not seated on mag-mount
  • Drafts from the wall cavity
  • Failed display

Test and repair steps

  1. Remove the HD display from the mag-mount and re-attach it.
  2. Seal the hole in the wall behind the mag-mount.
  3. Run Reset All in the dealer control center.
  4. Replace the HD display if it persists.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.46. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.