Lennox · Air conditioner
65544 More than 8 thermostats in a group
What the control is telling you
More than eight smart hubs assigned to one group; repeats every minute (dealer information). S30/S40 thermostat alert code 65544.
Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Too many hubs in one group
Test and repair steps
- Reassign smart hubs so a group has no more than eight (clears when five or fewer detected per manual).
Settings for these units
- Outdoor unit clearances · Lennox EL16KC1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.48. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.