Gree · Heat pump
P8 Inverter module overheated
What the control is telling you
The compressor drive module (IPM) got too hot, so the compressor stops.
Applies to: Gree Sapphire 9-24k (SAP..HP230V1A), Livo GEN4 30-36k (4LIV..HP230V1A), Vireo GEN3 9-24k (3VIR..HP115/230V1A), Multi21+ 18-24k multi-zone (MULTI..HP230V1CO), GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))
Likely causes
- Dried or missing thermal paste under the IPM
- Heat sink screws loose
- Poor outdoor airflow or very high load
- Board fault
Test and repair steps
- Warning: Kill power and let the outdoor board capacitors bleed down (about 20 min, or meter the DC bus below 20 V) before touching the inverter board.
- Check thermal paste between the IPM and heat sink and that the heat sink is tightly screwed down.
- Clean the outdoor coil and check the outdoor fan.
- If the code continues, replace the outdoor board.
Models that show this code
17 models in Gree Sapphire, Gree Livo GEN4, Gree Vireo GEN3, Gree Multi21+, Gree GMV6 Mini VRF
Other codes on the same units
- P3 Compressor intermediate-frequency test display
- P4 Compressor drive PFC protection
- P6 Compressor drive IPM protection
- P7 Inverter module temperature sensor fault
- P9 Inverter compressor lost synchronism
- U0 Compressor preheat not finished
- U1 Compressor phase current sensing fault
- U2 Outdoor capacity code / jumper wrong
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Gree Sapphire 9-12k (SAP09-12HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Sapphire 18-24k (SAP18-24HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Livo GEN4 30-36k (4LIV30-36HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Vireo GEN3 9-24k (3VIR..HP115-230V1A) service GREE_VIREOGEN3_SERVICE_090921.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Multi21+ multi-zone 18-24k (MULTI18-24HP230V1CO) service.pdf - section 9.1 Malfunction status sheet / 9.2 Malfunction Checking and Elimination; Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.