Gree · Heat pump

nb Outdoor and controller barcode query

Menu / mode display Gree GMV6 Mini VRF

What the display is showing

nb opens the barcode query. After choosing a module the display offers Un (unit barcode) or Pc (controller barcode) and then steps through the barcode in blocks: head, digits 1 to 6, digits 7 to 12 and digit 13. A parameter that does not exist shows 00.

Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))

What to do

  1. Hold SW2 on the master for over 5 seconds, select nb, confirm with SW3.
  2. Choose the module, then Un or Pc, then step through the barcode with SW1 and SW2.

Models that show this code

3 models in Gree GMV6 Mini VRF

GMV-V36WL/C-T(U)GMV-V48WL/C-T(U)GMV-V60WL/C-T(U)

Other codes on the same units

  • nE Negative number prefix
  • nF System mode: fan only
  • nH System mode: heating only
  • nJ High temperature prevention when heating (factory function)
  • nU Cancel indoor long-distance shielding (factory function)
  • nn Connection pipe length modification (factory function)
  • oC Commissioning step passed (OK)
  • oF Debugging finished / standby

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section 4.2.4.5 and Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.