Gree · Heat pump
Debug 01-17 Outdoor commissioning sequence (steps 01 to 17)
What the display is showing
On a new system or after the outdoor main board is replaced, the outdoor display walks through numbered commissioning steps shown as step/result (for example 02/Ad, 06/oC). A step with a fault shows the fault code next to the step number and the system resumes once it is cleared.
Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))
What to do
- Start when the board shows A0, hold SW3 for 5 seconds.
- 01 set master unit, 02 allocate addresses, 03 confirm outdoor quantity, 04 confirm indoor quantity (SW3 to confirm).
- 05 outdoor drive communication and capacity ratio, 06 outdoor components, 07 indoor components.
- 08 compressor preheat (SW3 may be used to confirm 8 hours have passed), 09 refrigerant check, 10 outdoor valve check (U6 shows if the valves are not fully open).
- 12 confirm start (AP, then AE), 15 cooling debug (AC) or 16 heating debug (AH), each passing after 50 minutes with no fault.
- 17 finished oF and standby.
Models that show this code
3 models in Gree GMV6 Mini VRF
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section 3.2.2.2 Test Operation and Debugging. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.