Gree · Heat pump
b4 Sub-cooler liquid outlet sensor open or shorted (20K)
What the control is telling you
The sub-cooler liquid outlet thermistor (20K, RT5, CN416) reads open or shorted.
Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))
Likely causes
- Sensor or plug fault
- Wire damage
- Board fault
Test and repair steps
- Turn off power and reseat the sensor plug.
- Measure the sensor and compare with the 20K resistance chart in the appendix.
- Replace the sensor if out of range; if good, replace the board that reads it.
Models that show this code
3 models in Gree GMV6 Mini VRF
Other codes on the same units
- A7 Outdoor silence mode (menu)
- A8 Vacuum mode (menu)
- A9 Set back function
- b1 Outdoor ambient sensor open or shorted (15K)
- b2 Defrost (coil) sensor open or shorted (20K)
- b6 Accumulator inlet sensor open or shorted (20K)
- C0 Communication fault IDU/ODU/wired controller
- C1 Main board to DC-DC controller communication fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.