Gree · Heat pump
0C Defaults restored (reset in progress)
What the display is showing
0C blinks on the master outdoor board while system defaults are being restored. The blink time shows which reset: 3 seconds for a full clear, 5 seconds for a clear that keeps the indoor and outdoor quantities and the commissioning status, and 7 seconds for the third variant that keeps engineering numbers, quantities and commissioning status.
Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))
What to do
- Full clear hold SW1 and SW4 for over 10 seconds (0C blinks 3 s).
- Clear that keeps quantities and commissioning status: hold SW2 and SW4 for over 10 seconds (0C blinks 5 s).
- Third variant (manual prints SW3 and SW4): hold for over 10 seconds (0C blinks 7 s).
Models that show this code
3 models in Gree GMV6 Mini VRF
Other codes on the same units
- 03/01 Commissioning step 03: confirming outdoor unit quantity
- 04/00-16 Commissioning step 04: indoor unit quantity
- 06 Commissioning step 06: checking outdoor components
- 07 Commissioning step 07: checking indoor components
- A0 Waiting for commissioning (status)
- A2 Pump-down (refrigerant recycle) mode
- A3 Defrosting
- A4 Oil return
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section 4.3 Restoration to Default Settings. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.