All 4 FAN lamps blink simultaneously All FAN lamps blinking together

Medium severity Air Purifier

What the control is telling you

Usually a missing filter, dust on the pre-filter, a blocked air outlet, or an electrical fault.

Applies to: MCB50YSAU

Likely causes

  • Pre-filter or dust collection filter not attached
  • Dust buildup on pre-filter
  • Air outlet blocked
  • Electrical component malfunction

Test and repair steps

  1. Check that the pre-filter and dust collection filter are attached. If one is missing, unplug, reattach it, and restart.
  2. If both are attached, check the pre-filter for dust. If dusty, unplug, clean it, and restart.
  3. Check the air outlet. If blocked, remove the obstacle and restart.
  4. If none of these apply, contact the place of purchase.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin MCB50YSAU installation & operation manual, p. 21. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.