Carrier · Mini-split
PC44 Zero speed protection
What the control is telling you
The outdoor unit sees no compressor speed.
Applies to: DLCM(R/H)B multi-zone outdoor units with DLFSHBH high wall indoor units (Midea, Carrier, Viessmann)
Likely causes
- Wiring
- Bad compressor
- Bad PCB
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Measure the input current on the supply wire. Limits: 15 A on 18K; 18.5 A on 27K and 18K high heat; 22.5 A on 36K and 27K high heat; 28 A on 48K and 36K high heat.
- Outdoor air above 122 F (50 C) = outside the range, shut it down.
- Check outdoor airflow and clean the coil.
- Check for a refrigerant restriction. If blocked: recover the charge, blow the lines through with nitrogen, evacuate and recharge.
- If none of the above, replace the outdoor main board (or the electric control box) and retest.
- Also check the compressor windings (see PC43).
Models that show this code
12 models in Carrier DLCM(R/H)B multi-zone outdoor, Carrier DLFSHB high wall indoor
Other codes on the same units
- PC40 Main chip to compressor drive chip communication error
- PC41 Current input detection protection
- PC42 Compressor start failure
- PC43 Compressor phase loss
- PC45 Compressor drive chip (IR / 341 PWM) failure
- PC46 Compressor speed out of control
- PC49 Compressor over-current
- PCA1 Refrigerant pipe condensation protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 23 Outdoor Unit Error Display p.26; diagnosis p.64-65; Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 p.17, p.39. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.